- Simple and easy to set
- Precise control performance and high dynamic response
- Pressure regulator built in to eliminate variations in supply air pressure
- Low air consumption due to piezo electric microvalve
- Input/ output signal isolated
- Simple conversion to direct acting (DA)or reverse acting(RA)
- Single and double acting available
- No hunting on the small actuators
- 1/2 split range available
- Position transmitter and limit switches to be built in one unit
- High resistance against shock and vibration |
| |
 |
- Position transmitter(4...20mA output signal)
- Limit switches (open and close at any two points)
- Gauge block with two stainless steel pressure gauges
- Explosion proof type (Exd ¥±B T6,Exia ¥±C T6) |
|
 |
|
|
SEL |
SER |
Linear Type |
Rotary Type |
Single |
Double |
Single |
Double |
Input Signal |
4...20mA, 2-wire |
Split Range Application |
8.5V DC @ 20mA (425§¤) |
Voltage Supply Min./Max. |
3.6mA / 50mA |
Characteristic |
1.4...7.0bar(20...100psi) / filtered compressed dry and non-oiled air |
Stroke | Angle |
5..80mm (max. up to 150mm) |
40...90¢ª (max.up to 100¢ª) |
Air Supply Pressure |
1.4...7.0bar(20...100psi) / filtered compressed dry and non-oiled air |
Air Consumption |
0.08§©/h at 1.4 bar input pressure |
| Output Pressure Range |
0...100% supply air pressure |
| Linearity |
Within ¡¾ 0.5% F.S |
| Hysteresis |
Within ¡¾ 0.2% F.S |
| Sensitivity |
Within ¡¾ 0.1% F.S |
| Operating Temperature |
-20¡É ...+70¡É |
| Pneumatic Connections |
Rc 1/4 or NPT 1/4 |
| Electrical Connections |
G 1/2 or NPT 1/2 |
| Body Material |
Aluminum diecast |
| Protection Class |
IP66, Intrinsic Safety (Exia), Flameproof (Exd) |
| Weight |
2.3kg / with pressure gauge block |
|
| |
 |
 |
¨ç Mount the positioner to the control as shown below
¨è Connect the feedback lever to control valve stem at position where the angle between the valve stem and the feedback lever becomes 90¢ª as shown below when the input signal is to 12mA (50%)
¨é Stroke range for the best performance should be 5~80mm and the operating angle of the feedback lever should be maximum 45¢ª to carry out accuracy perfectly |
|
 |
|
|
|
 |
 |
|
 |
¨ç Mount the multi-tupe barcket to the actuator as shown below
¨è Confirm the rotating direction of the actuator for air piping (see catalog and manual for details)
¨é Confirm if the feedback lever shaft "A" is placed in the orifice of the fork lever "B" and they are in perfect alignment with a rotary actuator output shaft |
 |
 |
 |
| |
 |
|
 |
| |
 |
 |
|
 |
|
 |
| Confirm the rotating direction of the actuator and connect the air lines as below |
 |
|
| |
Spring Return |
Double Acting |
| Reverse Acting |
Out1:piped, Out2:plugged |
Out1:piped to Actuator port A, Out2:piped to Actuator port B |
| Direct Acting |
Out1: plugged, Out2: piped |
Out1:piped to Actuator port B, Out2:piped to Actuator port A |
|
| |
 |
 |
Description |
Code |
Description |
Code |
Actuator Operation: |
L: Linear Type
R: Rotary Type |
Pressure Gauge Block: |
N: None
1: 6bar (90psi)
2: 10bar (150psi) |
Protection Class:
|
F: Flameproof(Exd ¥±B T6)
I: Intrinsic Safety(Exia ¥±B T6)
W: Weatherproof to IP 66 |
Position Feedback : |
N: None
O: Position Transmitter
(4~20mA Output Signal)
L: Two Alarm Limits
M: O+L |
Feedback Lever:
£ªLinear Type
£ªRotary Type |
A: Stroke (5~40 mm)
B: Stroke (5~80 mm)
C: Stroke (up to 150 mm)
F: Fork Lever (standard)
N: NAMUR Shaft (direct mounting) |
Mounting Bracket : |
N: None
L: DIN/IEC534(for SEL)
R: DIN VDI/VDE3845
(for SER) |
|
| |
 |
¨ç Supply 4mA input signal and set Zero by turning the zero screw on the control board until Zero reaches 0% of the valve / actuator
¨è Supply 20mA input signal and set Span by turning the span screw on the control board until Span reaches 100% of the valve / actuator |
|
 |
| |
 |
Input signal should be porvided for measurement of output signal.
¨ç With a mA loop calibrator Select Measurement mode and connect £« to 4 and £ to 5
¨è With a mulitimeter tester(mA) |
 |
| |
 |
 |
 |
|
 |
 |
| |
 |
|
 |